Lenel OnGuard Hardware Installation Manual page 105

Table of Contents

Advertisement

20.1.2
Hardware Flow Control
To configure the hardware flow control status, set DIP switches 4 and 5 according to the following table.
Leave this feature set to ON for Lantronix, dial-up, and RS-232, and OFF for RS-485 communication.
HANDSHAKE STATUS
Hardware Flow Control
None
20.1.3
Communication Baud Rate
To configure the communication baud rate, set DIP switches 6 and 7 according to the following table. DIP
switches 6 and 7 control the communication baud rate for port 1 only. Port 6 is fixed at 38400 bps.
BAUD RATE
6:
38400 bps
ON
19200 bps
off
9600 bps
ON
115,200 bps*
off
Note:
The 115,200 baud rate is supported for use with a Lantronix device. If using a direct connection to
the host workstation, refer to the OnGuard 7.3 Release Notes for supported operating systems.
In order to communicate with an ISC at 115,200 bps, an extra wire is required in the RS-232 cable,
connected to RTS/R1+.
For a 9-pin cable,
Jumper pins 4 and 6 together.
Connect pin 8 to RTS/R1+ on the LNL-2000.
DIP SWITCH 4
(for port 6):
ON
off
DIP SWITCH
7:
ON
ON
off
off
Hardware Installation Guide
DIP SWITCH 5
(for port 1):
ON
off
TXD
TR1+
RXD
TR1-
RTS
R1+
CTS
R1-
GND
105