Lenel OnGuard Hardware Installation Manual page 341

Table of Contents

Advertisement

NC
C
NO
NO
NC
C
63.1.4
Downstream Reader Communication
The Single Reader Interface Module can communicate downstream with one (1) keypad or card reader. The
J1 interface is a six-wire interface that includes a buzzer control wire and an LED control wire. The buzzer
wire is an open collector that produces 5 VDC open circuit maximum, and 10 mA sink maximum. The LED
wire provides between 0.05 and 3 V, 5 mA source/sink maximum.
Wire the J1 interface using a 24 AWG (minimum) cable at a maximum of 500 feet.
The reader power is a maximum of 80 mA. If the reader requires additional current, connect the reader
power to a +12 VDC terminal on the Single Reader Interface Module.
If you are connecting the reader to a dual reader interface module, each wire should be attached to the
associated connection on the Dual Reader Interface Module board (LNL-1320).
All readers that have a buzzer will beep during pre-alarm when in extended held open mode. This includes
primary and alternate readers. If the reader has two-wire LED control, this feature is disabled. The reader
starts beeping at pre-alarm time and continues to do so until the door is closed or the held open time is hit.
Relay Contact (AC Strike)
AC
XFMR
FOR 24 VAC STRIKE, PANASONIC ERZ-C07DK470
MOV SELECTION:
CLAMP VOLTAGE > 1.5 X VAC RMS
Hardware Installation Guide
AC STRIKE
341