Ul/Ulc Requirements - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

5.
From the Access Control menu, select Local I/O.
6.
On the Local I/O Function Lists form, create a Local I/O function for the Alarm Mask Group Mask/
Unmask group created in step 4.
7.
From the Access Control menu, select Groups.
8.
On the Mask Groups form, create an Intrusion Mask group for the desired alarm points.
9.
Link the Local I/O function for the Alarm Mask Group Mask/Unmask created in step
Mask group created in step
a.
For the Disarmed selection, set the Local Function created in step
Nothing for Exit".
b.
For Arming selections, set the local function created in step
Nothing for Exit".
10. From the Access Control menu, select Readers and Doors.
11. On the Aux Outputs form, add one (1) Auxiliary Output that will be wired to the local notification
chosen.
12. From the Access Control menu, select Global I/O. Create two (2) Global I/Os.
a.
Configure the first Global I/O with Timezone set to "Always" and the Input Event device for the
input added in step
selected for the relay added in step 11, and then set the Operation drop-down to "Activate".
b.
The second Global I/O will have Timezone of "Always" and the Input Event device for the input
added in step
2
with an event of "Input Unmasked". The Output Action will be "Device Output",
selected for the relay added in step 11, and then set the Operation drop-down to "Deactivate".
Note:
The LS Linkage Server Service is required to verify the host connection as configured above.
This allows you to route a configuration through the host to change the state of the chosen local
notification each time the Intrusion Mask group is armed or disarmed.
Note:
The reader aux inputs and outputs can also be added (as detailed in steps 1, 2, 10, and 11) from
the Alarm Panels configuration based on what the type of hardware is available. (From the
Access Control menu, select Alarm Panels.)
5.3

UL/ULC Requirements

The LNL-500 and LNL-1000 must be connected directly, through dial-up (a dedicated phone line must
be used), or through Ethernet to the computer.
The LNL-2000 must be connected through serial, dial-up, or Ethernet using a dedicated LAN. The
secondary path must be connected through dial-up using a dedicated phone line or dedicated LAN for
back up (dual signal line transmission).
The LNL-2210 must be connected through Ethernet only using a dedicated LAN.
The LNL-2220 and LNL-3300 must be connected through serial, dial-up, or Ethernet using a dedicated
LAN. The secondary path must be connected through dial-up using a dedicated phone line or dedicated
LAN for back up (dual signal line transmission).
8
via the Configure Actions option on the Intrusion Mask group form.
2
with an event of "Input Masked". The Output Action will be "Device Output",
Hardware Installation Guide
6
to the Intrusion
6
to "Set True for Enter" and "Do
6
to "Set False for Enter" and "Do
53
revision 7 —