Initial Ip Addressing Mode - Lenel OnGuard Hardware Installation Manual

Table of Contents

Advertisement

Jumpers
Set at
J3
n/a
J4
off
ON
J5
off
ON
J6
J7, J8, J9
232
485
J10
off
ON
J11
n/a
J12
n/a
J13
n/a
J14
n/a
J15
n/a
J16
n/a
J17
n/a
Note:
Observe POLARITY connection to LED. External current limiting is not required.
33.5

Initial IP Addressing Mode

Set the board for the desired initial IP addressing mode. The board can be initially configured using a fixed
static IP address or an IP address automatically assigned by a DHCP server.
Automatic Address Assignment By default, the IP address will be assigned by a DHCP server. The
DNS name is "MAC" followed by the characters of the unit's MAC address.
Fixed Static IP Address In order to use a fixed static IP address, Power up the board with DIP switch 2
ON and DIP switch 1 off. This default address cannot be changed. If this is chosen, the default static IP
address is 192.168.0.251.
To communicate with the board using this address, the computer must also be on the same subnet. Usually,
this requires changing the computer's network interface card settings.
Description
Factory use only
Port 2 RS-485 EOL terminator is off.
Port 2 RS-485 terminator is ON.
Port 3 RS-485 EOL terminator is off.
Port 3 RS-485 terminator is ON.
Connector for Lantronix CoBox-micro connection - port 1
Port 1 is RS-232
Port 1 is RS-485
Port 1 RS-485 EOL terminator is off.
Port 1 RS-485 terminator is ON.
Factory use only
Factory use only
Factory use only
Remote status LED #1 (see note below)
Remote status LED #2 (see note below)
Remote status LED #3 (see note below)
Remote status LED #4 (see note below)