LenelProx Readers
2.
Snap open the reader's top cover by inserting a screwdriver blade into the slot at the bottom edge of the
cover, then twisting the blade gently.
3.
Connect the reader to the access control panel according to the following figure(s). Tape or cap the
unused wires singly.
Wiring with reader interface modules:
Use the following tables to wire the LenelProx LPSL-6820 with either the single or dual reader
interface module. Since the current requirements for these readers range from 40 to 120 mA, this
means that the readers can be powered from the reader interface modules.
Wiring the LPSP-6820 and the LNL-1300
From LNL-1300
Reader
Pin
Terminal
GND
BZR
LED
TB4
CLK D1
DAT D0
V0
Wiring the LPSP-6820 and the LNL-1300-U
From LNL-1300-U
Reader
Pin
Terminals
GND
J10
DAT D0
CLK D1
LED1
LED2
J13
BZR
V0
500 —
revision 7
To LPSP-6820 Reader
Wire Color
Description
Black
Ground
Yellow
Beeper
Brown
LED
White
Data 1
Green
Data 0
Red
5 - 12 VDC
To LPSP-6820 Reader
Wire Color
Black
Ground
Green
Data 0
White
Data 1
Brown
Green LED
Not connected
Not connected
Yellow
Buzzer
Red
5-12 VDC
Typical Software Settings
Reader Type = Wiegand/Prox
Keypad = No Keypad
LED Mode = 1-Wire LED
Control
Typical Software Settings
Description
Reader Type =
Wiegand/Prox
Keypad = No Keypad
LED Mode = 1-Wire
LED Control

Advertisement