Lenel OnGuard Hardware Installation Manual page 26

Table of Contents

Advertisement

Hardware Installation Guidelines
Device
LNL-1100-U
LNL-1200
LNL-1200-U
LNL-1300
LNL-1300e
LNL-1300-U
LNL-1320
26 —
revision 7
Power Required
Note:
For UL installations, refer to section
page 296 for this device.
12 to 24 VDC ± 10%
12 VDC @ 300 mA nominal
24 VDC @ 150 mA nominal
12 to 24 VDC ± 10%, 1100mA maximum
12 VDC @ 850 mA nominal
24 VDC @ 450 mA nominal
Note:
For UL installations, refer to section
page 331 for this device.
12 to 24 VDC ± 10%
12 VDC @ 805 mA nominal
24 VDC @ 407 mA nominal
12 to 24 VDC + 10%, 150mA maximum (plus reader current)
12 VDC @ 110mA (includes reader current) nominal
24 VDC @ 60 mA (includes reader current) nominal
Note:
For UL installations: Refer to section
page 140 for this device.
Note:
For UL installations, PoE powered devices can be used if supply is
UL 294B rated.
12 VDC ± 10%, 200 mA minimum, 900 mA maximum
PoE power input 12.95W, compliant to IEEE 802.3af
Note:
For UL installations, refer to section
page 400 for this device.
12 to 24 VDC ± 10%
12 VDC @ 700 mA (includes reader current) nominal
24 VDC @ 350 mA (includes reader current) nominal
12 to 24 VDC + 10%, 550mA maxiumum (plus reader current)
12 VDC @ 450 mA (includes reader current) nominal
24 VDC @ 270 mA (includes reader current) nominal
UL Listed Installations
on
UL Listed Installations
on
UL Listed Installations
on
UL Listed Installations
on