The application software must be configured for elevator control. This can be done on the Elevator
Hardware tab in the Readers window of the System Administration software. The "Elevator" box should be
checked. The reader's type, name, port, address, access panel, can all be defined here.
With elevator control on the LNL-1300 reader, door strike and contact are not available, and REX (Request
to EXit) has been disabled.
Addresses assigned to input/output panels do not have to be consecutive. On the first panel, the inputs/
outputs represent the first sixteen floors (e.g.: Input 1 = first floor, Input 2 = second floor, etc.). The second
panel represents the next sixteen floors (floor 17 through 32), etc.
Maximum:
4000 feet
(1219.2 meters)
5 conductors
Single
Reader
Interface
Overview of Elevator Control
Access
Control
System
Intelligent System Controller
Single
Reader
Interface
Up to 128 Outputs -
Module
eight Output Control
Elevator
Reader
(inside cab)
Hardware Installation Guide
Output
Control
Module
Single Reader Interface
eight Input Control
Modules
Elevator Control Room
Input Control
Module
Up to 128 Inputs -
Modules
307