A2: User Parameters - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

6.
Drive returns to the parameter display.
7.
Press
and scroll to A1-01.
Press
to display the value set to A1-01. If the first "0" blinks, parameter settings
8.
are unlocked.
9.
Use
and
to change the value if desired. This is not typical.
10. Press
to save the setting, or
changes.
11. The display automatically returns to the parameter display.
Note:
Parameter settings can be edited after entering the correct password. Performing a 2-Wire or 3-Wire initialization resets the password
to "0000". Reenter the password to parameter A1-05 after drive initialization.
n
A1-06: Application Presets
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically sets the required parameters to default values and selects I/Os. In addition, Application
Preset parameters are assigned to the list of User Parameters, A2-01 through A2-16. These can be accessed in the Setup
Mode and provide quicker application adjustment by eliminating the need to scroll through multiple menus.
Refer to Application Selection on page 94
n
A1-07: DriveWorksEZ Function Selection
DriveWorksEZ is a software package that can be used to customize the drive functionality or add PLC functionality by
the interconnection and configuration of basic software function blocks. The drive performs program created by the user
in 2 ms cycles.
Parameter A1-07 can be used to enable or disable the DriveWorksEZ program inside the drive.
Note:
1. If DriveWorksEZ assigned functions to any multi-function output terminals, those functions stay set after disabling DriveWorksEZ.
2. Reinitialization using A1-03 does not reset A1-07 to the factory default value.
3. For more information on DriveWorksEZ, contact a Yaskawa representative or the Yaskawa sales department directly.
No.
A1-07
Setting 0: DWEZ Disabled
Setting 1: DWEZ Enabled
Setting 2: Digital Input
u

A2: User Parameters

n
A2-01 to A2-32: User Parameters
The user can select 32 parameters and assign them to A2-01 through A2-32. This saves time later scrolling through the
parameter menu. The list of User Parameters can also track the most recently edited settings and save those parameters to
this list.
No.
A2-01 to A2-32
Saving User Parameters
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2).
Next assign the parameter number to the User Parameters list by entering it into one of the A2-oo parameters. By then
setting A1-01 to "1", the access level can be restricted so that users can only set and reference the specific parameters
saved as User Parameters.
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Step
to return to the previous display without saving
for details on parameter A1-06.
Parameter Name
DriveWorksEZ Function Selection
Parameter Name
User Parameters 1 to 32
5.1 A: Initialization
Display/Result
Setting Range
0 to 2
Setting Range
A1-02; b1-01 to o2-08
Default
0
5
Default
Depending on
A1-06
115