European Standards; Ce Low Voltage Directive Compliance - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

D.2 European Standards
D.2 European Standards
The CE mark indicates compliance with European safety and environmental regulations and is required for engaging in
business and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
• Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives
displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure
compliance with CE standards. After setting up the device, verify that conditions meet European standards.
• Low Voltage Directive: 73/23/EEC, 93/68/EEC
u

CE Low Voltage Directive Compliance

This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage
Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other
devices:
n
Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN
664.
n
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with
UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
Table
D.1.
NOTICE: If a fuse is blown or an Earth Leakage Circuit Breaker (ELCB) is tripped, check the wiring and the selection of peripheral
devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Drive Model
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
BA0018
2A0001
2A0002
2A0004
2A0006
2A0008
2A0010
2A0012
2A0018
2A0020
2A0030
434
Figure D.1 CE Mark
Table D.1 Factory Recommended Drive Branch Circuit Protection
Model
Single-Phase 200 V Class
FWH-25A14F
FWH-25A14F
FWH-60B
FWH-80B
FWH-100B
FWH-125B
FWH-175B
Three-Phase 200 V Class
FWH-25A14F
FWH-25A14F
FWH-25A14F
FWH-25A14F
FWH-70B
FWH-70B
FWH-70B
FWH-90B
FWH-90B
FWH-100B
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Fuse Type
Manufacturer: Bussmann
Fuse Ampere Rating (A)
25
25
60
80
100
125
175
25
25
25
25
70
70
70
90
90
100

Hide quick links: