O: Operator Related Parameters - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

PRG: 1018 and later: 0% or 20 to 200%
PRG: 1017 and earlier: 20 to 200%
<4> Setting range varies depending on drive software version. Software versions PRG: 1018 and later allow this parameter to be changed during
run.
PRG: 1018 and later: -200.0 to 200.0%
PRG: 1017 and earlier: -200.0 to 0.0%
<5> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<6> Available in drive software versions PRG: 1018 and later. There is normally no need to change this parameter from the default value.
<7> Parameter available in drive software versions PRG: 1011 and later.
<8> Default setting is determined by drive model.
Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00.
Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50.
u

o: Operator Related Parameters

o parameters are used to set up the LED digital operator displays.
No.
Name
o1-01
Drive Mode Unit Monitor
<1>
Selection
o1-02
User Monitor Selection
<1>
After Power Up
Digital Operator Display
o1-03
Selection
o1-05
<1>
LCD Contrast Control
<7>
Frequency Reference Setting
o1-10
and User-Set Display
Frequency Reference
o1-11
Setting / Decimal Display
LO/RE Key Function
o2-01
Selection
STOP Key Function
o2-02
Selection
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Description
o1: Display Settings
Use o1 parameters to configure the digital operator display.
Switches the display after the power has been turned on.
When using an LED operator, pressing the up arrow key will
display the following data:
frequency reference → rotational direction → output
frequency → output current → output voltage → U1-oo.
(This is done by entering the 1oo part of U1-oo. Certain
monitors are not available in some control modes.)
Selects the information that is displayed when the power is
turned on.
1: Frequency Reference (U1-01)
2: Forward/Reverse
3: Output Frequency (U1-02)
4: Output Current (U1-03)
5: User Monitor (set by o1-01)
Sets the units to display the frequency reference and output
frequency.
0: Hz
1: % (100% = E1-04)
2: r/min (enter the number of motor poles into E2-04/E4-04/
E5-04)
3: User defined by parameters o1-10 and o1-11
Sets the brightness of the optional LCD operator.
These settings define the display values when o1-03 is set to
3.
o1-10 sets display values when operating at the maximum
output frequency.
o1-11 sets the position of the decimal positions.
o2: Operator Keypad Functions
Use o2 parameters to configure LED digital operator key functions.
Enables/Disables the digital operator LO/RE key.
0: Disabled
1: Enabled
Enables/Disables the operator panel STOP key when the
drive is operated form external sources (not operator).
0: Disabled
1: Enabled
B.2 Parameter Table
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
<2>
106
A A A
Set to U1-06 as a default (Output
Voltage Reference).
1 to 5
1
A A A
0 to 3
0
A A A
0 to 5
3
A A A
1 to
<3>
A A A
60000
<3>
0 to 3
A A A
0, 1
1
A A A
0, 1
1
A A A
Addr.
Pg.
Hex
500
235
501
235
502
235
504
236
520
236
521
236
505
236
B
506
236
367