LED Operator Display
oFA00
Cause
The option card is incompatible with the
drive.
LED Operator Display
oFA01
Cause
The option card is not connected properly to
the drive.
LED Operator Display
oFA03
oFA04
to
oFA30 to oFA43
Cause
Option card or hardware is damaged.
LED Operator Display
Cause
Surrounding temperature is too high.
Load is too heavy.
Internal cooling fan is stopped.
LED Operator Display
Cause
Surrounding temperature is too high.
Load is too heavy.
The internal cooling fan has reached its
performance life or has malfunctioned.
Current flowing to control circuit terminal
+V exceeded the tolerance level.
LED Operator Display
Cause
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Option Card Connection Error at Option Port CN5-A
The option card is incompatible with the drive.
Use a compatible option card.
Option Card Fault (Port A)
Replace the option card.
Turn the power off and reconnect the option card.
Option Card Fault (port A)
Option card self-diagnostic error
Option Card Fault (port A)
An error occurred attempting to write to the option card memory.
Option Card Fault (port A)
Communication ID error
Replace the option card. Contact Yaskawa for consultation.
Heatsink Overheat
oH
The temperature of the heatsink exceeded the value set to L8-02. Default value for L8-02 is determined
by drive capacity (o2-04).
• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.
• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).
• After replacing the drive, reset the cooling fan maintenance parameter (o4-03 = "0").
Overheat 1 (Heatsink Overheat)
oH1
The temperature of the heatsink has exceeded 10 °C plus the default value of L8-02.
• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.
• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.
• Check the maintenance time for the cooling fan (U4-04).
• After replacing fan, reset the fan maintenance time (o4-03 = "0").
• Check the current level of the terminal.
• Set the current to the control circuit terminal to be 20 mA or less.
Motor Overheat Alarm (PTC Input)
oH3
• The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level.
• Detection requires multi-function analog input H3-02 or H3-10 be set to "E".
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
6.4 Fault Detection
6
259