F6: Serial Communications Option Card Settings - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

5.6 F: Option Settings
n
F1-14: PG Open-Circuit Detection Time
Sets the time required to detect PGo if no pulse signal is present at terminal RP.
No.
F1-14
u

F6: Serial Communications Option Card Settings

These parameters configure communication option cards and communication fault detection methods.
n
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
No.
F6-01
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02
Setting 0: Always Detected
Setting 1: Detection During Run Only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
External Fault from Comm. Option Operation Selection
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-07: NetRef/ComRef Function Selection
Selects how multi-step speed inputs are treated when the NetRef command is set.
No.
F6-07
Setting 0: Multi-Step Speed Operation Disabled
If the NetRef command is selected, multi-step speed input frequency references are disabled. This is the same as Yaskawa
F7 drives.
Setting 1: Multi-Step Speed Operation Enabled
Multi-step speed inputs are active and can override the frequency reference from the communications option even when
the NetRef command is selected. This is the same as Yaskawa F7 drives.
174
Parameter Name
PG Open-Circuit Detection Time
Parameter Name
Communications Error Operation Selection
Parameter Name
External Fault from Comm. Option Selection
Parameter Name
Parameter Name
NetRef/ComRef Function Selection
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Setting Range
0.0 to 10.0 s
Setting Range
0 to 3
Setting Range
0 or 1
Setting Range
0 to 3
Setting Range
0 or 1
Default
2.0 s
Default
1
Default
0
Default
1
Default
0