C.4 Connecting to a Network
n
RS-422 Interface
Note:
1. Turn on DIP switch S2 on the drive located at the end of the network. Turn it off at all other slaves.
2. Set H5-07 to 0 when using the RS-422 interface.
u

Network Termination

The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in terminating resistance
that can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the terminating
resistance by setting DIP switch S2 to the ON position. Disable the terminating resistance on all slaves that are not located
at the network line end.
408
Figure C.4 RS-422 Interface
Figure C.5
illustrates the setting of DIP switch S2.