YASKAWA V1000 Technical Manual page 352

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

B.2 Parameter Table
H1-oo
Function
Setting
62
External Search Command 2
65
KEB Ride-Thru 1 (N.C.)
66
KEB Ride-Thru 1 (N.O.)
67
Communications Test Mode
68
High-Slip Braking
6A
Drive Enable
75
Up 2 Command
76
Down 2 Command
7A
KEB Ride-Thru 2 (N.C.)
7B
KEB Ride-Thru 2 (N.O.)
7C
Short-Circuit Braking (N.O.)
7D
Short-Circuit Braking (N.C.)
7E
Forward/Reverse Detection
90 to 96
DWEZ Digital Inputs 1 to 7
9F
DriveWorksEZ enable
<1> Available in drive software versions PRG: 1016 and later.
No.
Name
Terminal MA, MB and MC Function
H2-01
Selection (relay)
Terminal P1 Function Selection (open-
H2-02
collector)
Terminal P2 Function Selection (open-
H2-03
collector)
H2-06
Watt Hour Output Unit Selection
<1> The availability of certain functions depends on the control method used.
352
H1 Multi-Function Digital Input Selections
Closed: Activates Current Detection Speed Search from the frequency
reference b3-01 = 0. Activates Speed Estimation Type Speed search if
b3-01 = 0.
Open: KEB Ride-Thru 1 enabled
Closed: Normal operation
Open: Normal operation
Closed: KEB Ride-Thru 1 enabled
Tests the MEMOBUS/Modbus RS-485/422 interface.
Closed: High-Slip braking is executed. Drive stops.
Open: Drive disabled.
If this input is opened during run, then the drive will stop as specified by
parameter b1-03.
Closed: Ready for operation.
Open: Maintains the current frequency reference.
Closed: Increases or decreases the frequency reference.
UP 2 and Down 2 commands must be set in combination with each other.
The frequency reference source must be assigned to the operator (b1-01
= "0").
Open: KEB Ride-Thru 2 enabled
Closed: Normal operation
Open: Normal operation
Closed: KEB Ride-Thru 2 enabled
Open: Normal operation
Closed: Short-Circuit Braking
Open: Short-Circuit Braking
Closed: Normal operation
Direction of rotation detection (for V/f with Simple PG Feedback)
Reserved for DWEZ input functions
Open: DWEZ enabled
Closed: DWEZ disabled
H2: Multi-Function Digital Outputs
Use H2 parameters to assign functions to the multi-function digital outputs.
Refer to H2 Multi-Function Digital Output
Settings on page
setting values.
Sets the output units for the watt hours when
Watt Hour Pulse Output is selected as the
digital output (H2-01, H2-02, or H2-03 = 39).
Outputs a 200 ms pulse signal when the watt-
hour counter increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Description
Description
353
for a description of
Control
Mode
V/
f
O
O
O
O
O
O
O
O
O
O
-
-
O
O
O
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
E
A A A
0 to 192
0
A A A
<1>
2
A A A
0 to 4
0
A A A
Pg.
O
P
L
M
V
O
O
184
O
O
184
O
O
184
O
O
184
-
-
184
O
O
184
O
O
184
O
O
184
O
O
185
O
O
185
-
O
185
-
O
185
-
-
186
O
O
186
O
O
186
Addr.
Pg.
Hex
40B
186
40C
186
40D
186
437
195

Hide quick links:

Advertisement

Table of Contents