Setting 12: Timer Output
This setting configures a digital output terminal as output for the timer function.
for details.
Setting 13: Speed Agree 2 (f
Closes whenever the actual output frequency is within the Speed Agree Width (L4-04) of the current frequency reference
regardless of the direction.
Status
Open
Output frequency does not match the frequency reference while the drive is running
Closed
Output frequency is within the range of frequency reference ± L4-04
Note:
The detection works in both forward and reverse.
Speed Agree 2
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 216
detection width.
Setting 14: User Set Speed Agree 2 (f
Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-04) of
the programmed Speed Agree Level (L4-03). As the detection level L4-03 is a signed value, detection works in the specified
direction only.
Status
Open
Output frequency or frequency reference are outside the range of L4-03 ± L4-04
Closed
Output frequency and the frequency reference are both with in the range of L4-03 ± L4-04
Speed Agree 2
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 216
detection width.
Setting 15: Frequency Detection 3
Output is closed as long as the output frequency is below the detection level set in L4-03 plus the hysteresis set in L4-04.
It closes when the output frequency falls below L4-03. As the detection level L4-03 is a signed value, the detection works
in the specified direction only.
Status
Open
Output frequency exceeded L4-03 plus L4-04.
Closed
Output frequency is below L4-03 or has not exceeded L4-03 plus L4-04 yet.
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
/f
Agree 2)
ref
out
Frequency
reference
Output
frequency
OFF
ON
Figure 5.61 Speed Agree 2 Time Chart
/f
Agree 2)
ref
set
Output
frequency
Frequency
reference
User Set
OFF
ON
Figure 5.62 User Set Speed Agree 2 Example with Positive L3-04 Value
Refer to b4: Delay Timers on page 130
Description
L4-04
Description
L4-03
Output
frequency
+/- L4-04
Frequency
reference
Description
5.7 H: Terminal Functions
L4-04
for details on setting the
for details on setting the