2.2 Mechanical Installation

2.2
Mechanical Installation
This section outlines specifications, procedures, and environment for proper mechanical installation of the drive.
u

Installation Environment

To help prolong the optimum performance life of the drive, install the drive in the proper environment.
the appropriate environment for the drive.
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project
construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation.
Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive. Failure to comply could result in
erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
u

Installation Orientation and Spacing

Install the drive upright as illustrated in
A – Correct
38
Table 2.1 Installation Environment
Indoors
IP20/NEMA Type 1 enclosure: -10 °C to +40 °C
IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C
Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C
NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C
Drive reliability improves in environments without wide temperature fluctuations.
When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature
inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20 °C to +60 °C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Up to 1000 meters without derating; up to 3000 meters with output current, ambient temperature, and voltage derating.
Refer to Altitude Derating on page 327
2
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
Install the drive vertically to maintain maximum cooling effects.
Figure 2.1
A
Figure 2.1 Correct Installation Orientation
Conditions
for details.
to maintain proper cooling.
B
B – Incorrect
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Table 2.1
B
describes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents