Setting a Predefined V/f Pattern
Setting the V/f Pattern
Choose the V/f pattern that meets the application demands from the table below. Set the correct value to E1-03. The V/f
parameters E1-04 to E1-13 can only be monitored, not changed.
Note:
1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Parameter E1-03 is not reset when the drive is initialized.
Setting
Specification
0
1
(default setting)
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Heavy Duty 2
5
50 Hz, Heavy Duty 1
6
60 Hz, Heavy Duty 1
7
60 Hz, Heavy Duty 2
8
50 Hz, mid starting torque
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
The following tables show details on predefined V/f patterns.
The following graphs are for 200 V class drives; double the values for 400 V class drives.
Predefined V/f Patterns for 0.1 to 3.7 kW Drives
Setting = 0
50 Hz
200
16
12
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
200
35
8
0
1.3
25
50
Frequency (Hz)
Setting = 8
50 Hz
200
19
12
0
1.3 2.5
50
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Table 5.15 Predefined V/f Patterns
50 Hz
60 Hz
Table 5.16 Constant Torque Characteristics, Settings 0 to 3
60 Hz
Setting = 1
(default)
200
16
12
0
1.5 3
60
Frequency (Hz)
Table 5.17 Derated Torque Characteristics, Settings 4 to 7
Setting = 5
50 Hz
200
50
9
0
1.3
25
50
Frequency (Hz)
Table 5.18 High Starting Torque, Settings 8 to B
Setting = 9
50 Hz
200
24
13
0
1.3 2.5
50
Frequency (Hz)
Characteristic
For general purpose applications. Torque remains
Constant torque
constant regardless of changes to speed.
For fans, pumps, and other applications that require
Derated torque
torque derating relative to the load.
Select high starting torque when:
• Wiring between the drive and motor exceeds
High starting torque
• A large amount of starting torque is required
• An AC reactor is installed
When operating at greater than 60 Hz the output
Constant output
voltage will be constant.
Setting = 2
200
16
12
0
1.5 3
Frequency (Hz)
Setting = 6
200
35
8
0
1.5
30
Frequency (Hz)
Setting = A
200
19
12
0
1.5 3
Frequency (Hz)
5.5 E: Motor Parameters
Application
150 m
60 Hz
Setting = 3
200
16
12
50
60
0
1.5 3
Frequency (Hz)
60 Hz
Setting = 7
200
50
9
60
0
1.5
30
Frequency (Hz)
60 Hz
Setting = B
200
24
15
60
0
1.5 3
Frequency (Hz)
72 Hz
60
72
60 Hz
5
60
60 Hz
60
163