A.2 Single/Three-Phase 200 V Class Drive
Three-Phase Drive Model
Single-Phase Drive Model
Maximum Motor Size Allowed (kW)
Input
Input
Current (A)
<3>
Rated Output Capacity
(kVA)
Output Current (A)
Output
Max Output Voltage (V)
Max Output Frequency (Hz)
Power
Supply
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Harmonic Corrective
Actions
<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor.
<2> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor rated current.
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency.
<6> DC is not available for UL standards.
<7> Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency.
Note:
Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current,
overload capacity, carrier frequency and current limit. Set parameter C6-01 to "0" for HD or "1" for ND (default).
320
Table A.3 Power Ratings Continued
Item
<1>
ND Rating
<2>
HD Rating
ND Rating
Three-Phase
HD Rating
ND Rating
Single-Phase
HD Rating
ND Rating
<4>
HD Rating
ND Rating
HD Rating
Overload Tolerance
Carrier Frequency
Rated Voltage
Rated Frequency
DC Reactor
2A0030
-
7.5
5.5
37.0
24.0
-
-
11.4
9.5
<5>
30.0
<7>
25.0
ND Rating: 120% of rated output current for 1 minute
HD Rating: 150% of rated output current for 1 minute
(Derating may be required for applications that start and stop frequently)
(both proportional to input voltage)
Three-phase power: 200 to 240 V 50/60 Hz
Single-phase power: 200 to 240 V 50/60 Hz
DC power supply: 270 to 340 V
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Specification
2A0040
2A0056
-
-
11.0
15.0
7.5
11.0
52.0
68.0
37.0
52.0
-
-
-
-
15.2
21.3
12.6
17.9
40.0
56.0
<7>
<7>
33.0
47.0
2 kHz (user-set, 2 to 15 kHz)
Three-phase power: 200 to 240 V
Single-phase power: 200 to 240 V
400 Hz (user-adjustable)
-15 to 10%
±5%
Optional
2A0069
-
18.5
15.0
80.0
68.0
-
-
26.3
22.9
69.0
<7>
60.0
<6>

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents