A2: User Parameters - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

5.1 A: Initialization
10.
Press
to save the setting, or press
11.
The display automatically returns to the parameter display.
Note:
1. Parameter settings can be edited after entering the correct password.
2. Performing a 2-Wire or 3-Wire initialization resets the password to "0000".
n
A1-06: Application Preset
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters
to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
u

A2: User Parameters

n
A2-01 to A2-32: User Parameters 1 to 32
The user can select up to 32 parameters and assign them to parameters A2-01 through A2-32 to provide quicker access by
eliminating the need to scroll through multiple menus. The User Parameter list can also save the most recently edited
parameters.
No.
A2-01 to A2-32
Saving User Parameters
To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then enter
the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01 to 1 to
restrict access so users can only set and refer to the parameters saved as User Parameters.
n
A2-33: User Parameter Automatic Selection
Determines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to A2-32) for
quicker access.
No.
A2-33
Setting 0: Do not save list of recently edited parameters
Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.
Setting 1: Save list of recently edited parameters
Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are saved
with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the User Parameters
using the Setup Mode of the digital operator.
146
Step
to return to the previous display without saving changes.
Parameter Name
User Parameters 1 to 32
Parameter Name
User Parameter Automatic Selection
Setting Range
b1-01 to s6–07
Setting Range
0, 1
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Display/Result
Entry Accepted
-PRMSET-
PRG
Init Parameters
A1-03= 0
0
No Initialize
FWD
Default
Determined by
A1-03
Default
0