5.7 H: Terminal Functions

5.7

H: Terminal Functions

H parameters are used to assign functions to the external terminals.
u

H1: Multi-Function Digital Inputs

n
H1-01 to H1-07: Functions for Terminals S1 to S7
These parameters assign functions to the multi-function digital inputs. Settings 0 to 9F determine function for each terminal
and are explained below.
Note:
1. Terminals that are not used and terminals using the through-mode should be set to "F".
2. Drive software versions PRG: 1013 and later require that the Forward run and Reverse Run commands be set simultaneously.
No.
Parameter Name
H1-01
Digital Input S1 Function Selection
H1-02
Digital Input S2 Function Selection
H1-03
Digital Input S3 Function Selection
H1-04
Digital Input S4 Function Selection
H1-05
Digital Input S5 Function Selection
H1-06
Digital Input S6 Function Selection
H1-07
Digital Input S7 Function Selection
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Setting
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
2
External Reference 1/2
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (oH2)
C
Terminal A1/A2 Enable/Disable
F
Not used/Through Mode
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast-Stop (N.O.)
16
Motor 2 Selection
17
Fast-stop (N.C.)
18
Timer Function Input
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F
External Fault
30
PID Integral Reset
31
PID Integral Hold
<1> Available in drive software versions PRG: 1016 and later.
176
Table 5.25 Digital Multi-Function Input Settings
Function
Setting
Range
1 to 9F
40: Forward Run Command (2-wire sequence)
1 to 9F
41: Reverse Run Command (2-wire sequence)
0 to 9F
24: External Fault (N.O., always detected, coast to stop)
0 to 9F
14: Fault Reset
<1>
0 to 9F
3 (0)
: Multi-Step Speed Reference 1
<1>
0 to 9F
4 (3)
: Multi-Step Speed Reference 2
<1>
0 to 9F
6 (4)
: Jog Reference Selection
Page
Setting
177
32
Multi-Step Speed Reference 4
177
34
PID Soft Starter Cancel
177
35
PID Input Level Selection
40
Forward Run/Stop (2-wire sequence)
178
41
Reverse Run/Stop (2-wire sequence)
42
Run/Stop (2-Wire sequence 2)
178
43
FWD/REV (2-Wire sequence 2)
178
44
Offset Frequency 1 Addition
45
Offset Frequency 2 Addition
178
46
Offset Frequency 3 Addition
178
<1>
Node Setup
47
178
60
DC Injection Braking Command
178
61
External Speed Search Command 1
179
62
External Speed Search Command 2
65
KEB Ride-Thru 1 (N.C.)
179
66
KEB Ride-Thru 1 (N.O.)
67
Communications Test Mode
180
68
High-Slip Braking
180
6A
Drive Enable
180
75
Up 2 Command
181
76
Down 2 Command
180
7A
KEB Ride-Thru 2 (N.C.)
181
7B
KEB Ride-Thru 2 (N.O.)
181
7C
Short-Circuit Braking (N.O.)
181
7D
Short-Circuit Braking (N.C.)
181
Forward/Reverse Detection (V/f Control with
7E
Simple PG Feedback)
181
90 to 96
DriveWorksEZ Digital Inputs 1 to 7
182
9F
DriveWorksEZ Disable
182
183
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Default
Function
Page
183
183
183
183
183
183
183
183
184
184
184
184
184
184
185
185
186
186
186