A.3 Three-Phase 400 V Class Drives
Item
Three-Phase Drive Model
Maximum Applicable Motor Capacity
<1>
(kW)
Input
Input Current (A)
Output Current (kVA)
Output Current (A)
Output
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Rated Frequency
Power
Supply
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Harmonic Corrective Actions
<1> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
<6> DC is not available for UL standards.
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Table A.4 Power Ratings
ND Rating
HD Rating
ND Rating
<2>
HD Rating
<4>
ND Rating
<3>
<5>
HD Rating
<4>
ND Rating
<5>
HD Rating
Rated Voltage
DC Reactor
A.3 Three-Phase 400 V Class Drives
Specification
4A0001
4A0002
4A0004
0.37
0.75
1.5
0.37
0.55
1.1
1.2
2.1
4.3
1.2
1.8
3.2
0.9
1.6
3.1
0.9
1.4
2.6
1.2
2.1
4.1
1.2
1.8
3.4
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
2 kHz (user-adjustable from 2 to 15 kHz)
Three-phase power: 380 to 480 V (proportional to input voltage)
400 Hz (user-adjustable)
Three-phase power: 380 to 480 V 50/60 Hz
DC power supply: 510 to 680 V
4A0005
4A0007
4A0009
2.2
3.0
4.0
1.5
2.2
3.0
5.9
8.1
9.4
4.4
6.0
8.2
4.1
5.3
6.7
3.7
4.2
5.5
5.4
6.9
8.8
4.8
5.5
7.2
<6>
-15 to 10%
±5%
Optional
4A0011
5.5
3.7
14.0
10.4
8.5
7.0
11.1
9.2
A
321