B.7 Parameters that Change with the Motor Code Selection
n
Drive Software Version PRG: 1018 and Later
Par.
Description
Motor Code
Voltage Class
E5-01
Rated Power
Rated Speed
E5-02 Motor Rated Power
E5-03 Motor Rated Current
E5-04 Motor Pole Number
Motor Winding
E5-05
Resistance
E5-06 d-Axis Inductance
E5-07 q-Axis Inductance
Induction Voltage
E5-09
mVs/rad
Constant 1
Induction Voltage
E5-24
Constant 2
Maximum Output
E1-04
Frequency
Maximum Output
E1-05
Voltage
E1-06 Base Frequency
Minimum Output
E1-09
Frequency
Motor Acceleration
L3-24
Time for Inertia
<1>
Calculations
d-Axis Current for
n8-49
High-Efficiency
Control
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
394
Table B.14 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Unit
1232
1233
400 Vac
400 Vac
0.4 kW
0.75 kW
r/min
1750
1750
kW
0.4
0.75
A
0.89
1.56
6
6
Ω
25.370
9.136
mH
169.00
92.08
mH
197.5
119.56
392.6
440.6
mV/(r/
0
0
min)
Hz
87.5
87.5
V
380
380
Hz
87.5
87.5
Hz
4.4
4.4
s
0.092
0.076
%
–8.6
–11.5
Default Settings
1235
1236
1238
400 Vac
400 Vac
400 Vac
1.5 kW
2.2 kW
3.7 kW
1750
1750
1750
1.5
2.2
3.7
2.81
4.27
7.08
6
6
6
6.010
3.297
1.798
67.71
34.40
32.93
81.71
54.00
37.7
478.3
466.3
478.8
0
0
0
87.5
87.5
87.5
380
380
380
87.5
87.5
87.5
4.4
4.4
4.4
0.051
0.066
0.075
–10.3
–19.8
–8.5
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
123A
123B
123D
400 Vac
400 Vac
400 Vac
5.5 kW
7.5 kW
11 kW
1750
1750
1750
5.5
7.5
11
10.31
13.65
20.7
6
6
6
0.982
0.786
0.349
22.7
16.49
13.17
26.8
23.46
15.60
478.1
520.0
481.5
0
0
0
87.5
87.5
87.5
380
380
380
87.5
87.5
87.5
4.4
4.4
4.4
0.083
0.077
0.084
–11
–18.6
–12.5
123E
123F
400 Vac
400 Vac
15 kW
18 kW
1750
1750
15
18.5
27.5
33.4
6
6
0.272
0.207
10.30
8.72
12.77
11.22
498.8
509.5
0
0
87.5
87.5
380
380
87.5
87.5
4.4
4.4
0.102
0.101
–15.5
–17.9

Hide quick links: