C6: Carrier Frequency

n
C6-01: Drive Duty Selection
The drive has two different duty modes from which to select based on the load characteristics. The drive rated current,
overload capacity, and carrier frequency will change depending upon the duty mode selection. Use parameter C6-01 to
select Heavy Duty (HD) or Normal Duty (ND) for the application. The default setting is ND.
Normal Duty Ratings on page 318
No.
C6-01
<1> Model BA0018 does not have a Normal Duty mode. The default setting is 0.
Mode
C6-01
Characteristics
Application
Over load capability (oL2)
L3-02 Stall Prevention
during Acceleration
L3-06 Stall Prevention
during Run
Default Carrier
Frequency
Note:
By changing the Drive Duty, the drive maximum applicable motor power changes and the E2-oo and E4-oo parameters are
automatically set to appropriate values.
150
Parameter Name
ASR Proportional Gain 2
ASR Integral Time 2
Parameter Name
ASR Limit
for details about the rated current.
Parameter Name
Drive Duty Selection
Table 5.11 Differences between Heavy and Normal Duty
Heavy Duty Rating (HD)
0
Overload
150 %
Rated Load
100 %
0
Motor Speed
Use Heavy Duty Rating for applications requiring a high
overload tolerance with constant load torque. Such
applications include extruders and conveyors.
150% of drive rated Heavy Duty current for 60 s
150%
150%
8/10 kHz
100 %
Use Normal Duty Rating for applications in which the
torque requirements drop along with the speed. Examples
include fans or pumps where a high overload tolerance is
not required.
120% of drive rated Normal Duty current for 60 s
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Setting Range
0.00 to 300.00
0.000 to 10.000 s
Setting Range
0.0 to 20.0%
Refer to Heavy Duty and
Setting Range
0 or 1
Normal Duty Rating (ND)
1
Overload
120 %
Rated Load
100 %
0
Motor Speed
120%
120%
2 kHz Swing PWM
Default
0.02
0.050 s
Default
5.0%
Default
1
<1>
100 %