d2: Frequency Upper/Lower Limits

By entering upper or lower frequency limits, the drive programmer can prevent operation of the drive above or below
levels that may cause resonance and or equipment damage.
n
d2-01: Frequency Reference Upper Limit
Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No.
d2-01
n
d2-02: Frequency Reference Lower Limit
Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is input, the drive will run at the d2-02 level. If the drive is started with a lower reference
than d2-02, it will accelerate up to d2-02.
No.
d2-02
n
d2-03: Master Speed Reference Lower Limit
Unlike frequency reference lower limit (d2-02) which will affect the frequency reference no matter where it is sourced
from (i.e., analog input, preset speed, Jog speed, etc.), the master speed lower limit (d2-03) sets a lower limit that will only
affect the analog input (terminals A1 and A2) that is the active master speed frequency.
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
d1-05
d1-04
d1-03
d1-02
(A2)
d1-01
(A1)
FWD (REV) Run/Stop
ON
ON
ON
Figure 5.33 Preset Reference Timing Diagram
Parameter Name
Frequency Reference Upper Limit
Parameter Name
Frequency Reference Lower Limit
Internal frequency
reference
d2-01
Operating
range
d2-02
Figure 5.34 Frequency Reference: Upper and Lower Limits
d1-15
d1-14
d1-13
d1-12
d1-07
d1-06
ON
ON
ON
ON
ON
ON
ON
ON
ON
Setting Range
Setting Range
Frequency Reference Upper Limit
Frequency Reference Lower Limit
Set frequency reference
5.4 d: Reference Settings
d1-16
d1-17
Time
ON
ON
ON
Default
0.0 to 110.0%
100.0%
Default
0.0 to 110.0%
5
0.0%
155