Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit Programming During Run
It is not possible to enter the Programming Mode as long as the drive output is active.
n
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
No.
b1-14
Setting 0: Standard Phase Order
Setting 1: Switched Phase Order
n
b1-15: Frequency Reference Selection 2
Refer to b1-01: Frequency Reference Selection 1 on page 117
The value set to b1-15 is used as Frequency Reference 2 when one of the multi-function input terminals set for Frequency
Reference Switching (H1-oo = 2) closes.
instructions on how this function works.
No.
b1-15
n
b1-16: Run Command Selection 2
Refer to b1-02: Run Command Selection 1 on page 119
The value set to b1-16 is used as Run Command Source 2 when one of the multi-function input terminals set for Frequency
Reference Switching (H1-oo = 2) closes.
instructions on how this function works.
No.
b1-16
n
b1-17: Run Command at Power Up
This parameter is used to determine whether an external Run command that is active during power up of the drive will
start the drive or not.
No.
b1-17
Setting 0: Run Command at Power Up is not Issued
The Run command has to be cycled to start the drive.
Note:
For safety reasons, the drive is initially set up not to accept a Run command at power up (b1-17 = "0"). If a Run command is issued at
power up, the RUN indicator LED will flash quickly. Change parameter b1-17 to 1 if a Run command active at power up shall be
accepted by the drive.
Setting 1: Run Command and Power Up is Issued
An external Run command active during power up is issued and the drive starts to operate the motor as soon as it gets
ready for operation (i.e. once the internal start up process is complete).
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will
begin rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe
prior to powering up the drive. Failure to comply may cause serious injury.
u

b2: DC Injection Braking

These parameters determine how the DC Injection Braking/Short Circuit Braking feature operates. Parameters involving
the starting frequency, current level, braking time are located here.
n
b2-01: DC Injection Braking Start Frequency
Active when "Ramp to Stop" is selected as the stopping method (b1-03 = 0). Sets the starting frequency for:
• DC Injection Braking at stop in V/f and OLV control.
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Parameter Name
Phase Order Selection
Refer to Setting 2: External Reference 1/2 Selection on page 177
Parameter Name
Frequency Reference Selection 2
Refer to Setting 2: External Reference 1/2 Selection on page 177
Parameter Name
Run Command Selection 2
Parameter Name
Run Command at Power Up
Setting Range
for details.
Setting Range
for details.
Setting Range
Setting Range
5.2 b: Application
Default
0 or 1
0
for
Default
0 to 4
0
for
Default
0 to 3
0
Default
0 or 1
0
5
123