YASKAWA V1000 Technical Manual page 152

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

5.3 C: Tuning
Setting a Variable Carrier Frequency (V/f Control only)
In V/f Control, the carrier frequency can be set up to change linearly with the output frequency. In this case the upper and
lower limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) have to be set as
shown in
Figure
5.31.
K is a coefficient determined by the value of C6-03:
• 10.0 kHz > C6-03 ≥ to 5.0 kHz: K = 2
• 5.0 kHz > C6-03: K = 1
• C6-03 ≥ 10.0 kHz: K = 3
Note:
1. A carrier frequency error (oPE11) will occur when the carrier frequency proportional gain is greater than 6 while C6-03 is less than
C6-04.
2. When C6-05 is set lower than 7, C6-04 is disabled and the carrier frequency will be fixed to the value set in C6-03.
n
Rated Current Depending on Carrier Frequency
The tables below show the drive output current depending on the carrier frequency settings. The 2 kHz value is equal to
the Normal Duty rated current, the 8/10 kHz value is equal to the Heavy Duty rated current. The carrier frequency
determines the output current linearly. Use the data below to calculate output current values for carrier frequencies not
listed in the tables.
Note:
In Heavy Duty mode the maximum rated output current is equal to the 8/10 kHz value, even if the carrier frequency is reduced.
200 V Single-Phase Units
Drive
Model
2 kHz
BA0001
1.2
BA0002
1.9
BA0003
3.5
BA0006
6.0
200 V Single-Phase Units
Rated Current [A]
Drive
Model
2 kHz
8 kHz
BA0010
9.6
8.0
BA0012
12.0
11.0
BA0018
17.5
17.5
152
Carrier Frequency
C6-03
C6-04
Figure 5.31 Carrier Frequency Changes Relative to Output Frequency
Table 5.12 Drives with Heavy Duty Default Carrier Frequency of 10 kHz
Rated Current [A]
10 kHz
15 kHz
0.8
1.6
3.0
5.0
Table 5.13 Drives with Heavy Duty Default Carrier Frequency of 8 kHz
200 V Three-Phase Units
Drive
Model
15 kHz
6.4
2A0008
8.8
2A0010
14.0
2A0012
2A0018
2A0020
2A0030
2A0040
2A0056
2A0069
Output
x C6-05 x K*
Frequency
E1-04
Max Output Frequency
Drive
Model
0.6
2A0001
1.3
2A0002
2.4
2A0004
4.0
2A0006
Rated Current [A]
2 kHz
8 kHz
15 kHz
8.0
6.9
5.5
9.6
8.0
6.4
12.0
11.0
8.8
17.5
14.0
11.2
19.6
17.5
14.0
30.0
25.0
20.0
40.0
33.0
26.4
56.0
47.0
37.6
69.0
60.0
48.0
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Output Frequency
200 V Three-Phase Units
Rated Current [A]
2 kHz
10 kHz
1.2
0.8
1.9
1.6
3.5
3.0
6.0
5.0
400 V Three-Phase Units
Rated Current [A]
Drive
Model
2 kHz
4A0001
1.2
4A0002
2.1
4A0004
4.1
4A0005
5.4
4A0007
6.9
4A0009
8.8
4A0011
11.1
4A0018
17.5
4A0023
23.0
4A0031
31.0
4A0038
38.0
15 kHz
0.6
1.3
2.4
4.0
8 kHz
15 kHz
1.2
0.7
1.8
1.1
3.4
2.0
4.8
2.9
5.5
3.3
7.2
4.3
9.2
5.5
14.8
8.9
18.0
10.8
24.0
14.4
31.0
18.6