E2: Motor 1 Parameters - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

n
V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if E1-03 =< 15 or set up a custom
V/f pattern as shown in
Figure 5.42
No.
E1-04
E1-05
E1-06
E1-07
E1-08
<3>
E1-09
E1-10
E1-11
E1-12
<4>
E1-13
<1> Default setting is determined by the control mode.
<2> Values shown are for 200 V class drives; double the value when using 400 V class drives.
<3> In OLV for PM E1-09 specifies the start frequency for short circuit braking at stop.
125
for details.
<4> When E1-13 is set to 0.0 V, the drive uses the value set in E1-05 to control the voltage.
<5> Default setting is determined by E5-01 in OLV/PM. When E5-01 is set to FFFFH, the setting range for E1-04 and E1-06 is 10.0 to 40.0 Hz
and the setting range for E1-09 is 0.0 to 400.0 Hz.
<6> The default value is for the following localized drives: Japan (Model code: CIMR-VAoA) and Asia (Model code: CIMR-VToA).
China Localized Drive Default Values on page 381
Note:
1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. Setting E1-11 to 0 disables both E1-11 and E1-12 and the above conditions do not apply.
3. To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
4. E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned to
their default values.
u

E2: Motor 1 Parameters

These parameters contain the most important motor data needed for optimal motor control. They are set automatically
when Auto-Tuning is performed. If Auto-Tuning can not be performed, then these parameters can be set manually.
n
E2-01: Motor Rated Current
Set E2-01 to the full load amps (FLA) stamped on the motor nameplate. During Auto-Tuning the value must be entered
to parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E2-01.
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
when E1-03 = F.
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
for the default values of China localized (Model code: CIMR-VBoA) drives.
Output Voltage (V)
Figure 5.42 V/f Pattern
Setting Range
40.0 to 400.0 Hz
0.0 to 255.0 V
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 255.0 V
0.0 to 400.0 Hz
0.0 to 255.0 V
0.0 to 400.0 Hz
0.0 to 255.0 V
0.0 to 255.0 Hz
Refer to b2-13: Short Circuit Brake Time at Stop on page
Frequency (Hz)
5.5 E: Motor Parameters
Default
<5>
<1> <6>
<2>
<1>
<5>
<1> <6>
<1> <6>
<2>
<1>
<5>
<1> <6>
<2>
<1>
0.0 Hz
<2>
0.0 V
0.0 V
Refer to
165
5

Hide quick links: