A2: User Parameters - YASKAWA A1000 Technical Manual

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

A1-07: DriveWorksEZ Function Selection
DriveWorksEZ is a software package that can be used to customize the drive functionality or add PLC functionality by
the interconnection and configuration of basic software function blocks. The drive performs programs created by the user
in 1 ms cycles.
Parameter A1-07 can be used to enable or disable the DriveWorksEZ program inside the drive.
Note: 1. If DriveWorksEZ has assigned functions to any multi-function output terminals, those functions will remain set to those terminals
even after disabling DriveWorksEZ.
2. For more information on DriveWorksEZ, contact a YASKAWA representative or the YASKAWA sales department directly.
No.
A1-07
Setting 0: DWEZ disabled
Setting 1: DWEZ enabled
Setting 2: Digital input
If a digital input is programmed for DWEZ enable/disable (H1- = 9F), DWEZ will be enabled when the input is
opened.
 A2: User Parameters
A2-01 to A2-32: User Parameters 1 to 32
The user can select 32 parameters and assign them to A2-01 through A2-32. This saves time later scrolling through the
parameter menu. The list of User Parameters can also track the most recently edited settings and save those parameters to
this list.
No.
A2-01 to A2-32
<1> This is the default setting of the Setup Mode parameters.
<2> A1-06 determines how parameters edited by the user are saved to the list of User Parameters, A2-01 through A2-32. Refer to
Selection on page 114
for details.
Saving User Parameters
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2).
Next assign the parameter number to the User Parameters list by entering it into one of the A2- parameters. If A1-01
is then set to 1 and changed to Setup Mode, the access level can be restricted so that users can only set and refer to the
specific parameters saved as User Parameters.
A2-33: User Parameter Automatic Selection
A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for
quick, easy access.
No.
A2-33
Setting 0: Do not save list of recently viewed parameters.
To manually select the parameters listed in the User Parameter group, set A2-33 to 0.
Setting 1: Save history of recently viewed parameters.
By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A
total of 16 parameters are saved with the most recently edited parameter set to A2-17, the second most recently to A2-18,
and so on. User Parameters can be accessed using the Setup Mode of the digital operator.
Note: User parameter is listed from A2-27 as A2-01 to A2-26 are already listed as default setting when in Setup Mode.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Parameter Name
DriveWorksEZ Function Selection
Parameter Name
User Parameters 1 to 32
Table 4.4
for details.
Parameter Name
User Parameter Automatic Selection
5.1 A: Initialization
Setting Range
Default
0 to 2
Setting Range
Default
A1-00 to o4-13
Application
Setting Range
Default
0 or 1
Determined by A1-06
0
<1> <2>
5
147

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents