YASKAWA V1000 Technical Manual page 372

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

B.2 Parameter Table
No.
Name
U1-03
Output Current
U1-04
Control Mode
U1-05
Motor Speed
U1-06
Output Voltage Reference
U1-07
DC Bus Voltage
U1-08
Output Power
U1-09
Torque Reference
U1-10
Input Terminal Status
U1-11
Output Terminal Status
U1-12
Drive Status
U1-13
Terminal A1 Input Level
U1-14
Terminal A2 Input Level
372
Description
Displays the output current.
Control method set in A1-02.
0: V/f without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
Displays the motor speed feedback. Display units are
determined by o1-03.
Displays the output voltage.
Displays the DC bus voltage.
Displays the output power (this value is determined
internally).
Monitor of internal torque reference value for Open Loop
Vector (OLV) control
Displays the input terminal status.
Digital input terminal
S1 enabled
Digital input terminal
S2 enabled
Digital input terminal
S3 enabled
Digital input terminal
S4 enabled
Digital input terminal
S5 enabled
Digital input terminal
S6 enabled
Digital input terminal
S7 enabled
Displays the output terminal status.
Multi-Function
Digital Output (fault)
(terminal MA/MB-MC)
Multi-Function
Digital Output 1
(terminal P1) enabled
Multi-Function
Digital Output 2
(terminal P2) enabled
Verifies the drive operation status.
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
Displays analog input A1 level: 100% when input is 10 V. 10 V: 100%
Displays analog input A2 level: 100% when input is 10 V. 10 V: 100%
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Control
Mode
Analog Output
Unit
Level
V/
f
0.01
A
10 V: Drive rated
A A A
<1>
current
<2>
No output signal
A A A
available
10 V: Maximum
0.01
– A –
speed
Hz
10 V: 200 Vrms
0.1 V A A A
(400 Vrms)
10 V: 400 V (800
1 V
A A A
V)
10 V: Drive
capacity (kW)
<1>
A A A
(rated motor
capacity)
10 V: Motor rated
– A –
torque
No output signal
A A A
available
No output signal
A A A
available
No output signal
A A A
available
0.1% A A A
0.1% A A A
Addr.
O
Hex
P
L
M
V
42
43
44
45
46
47
48
49
4A
4B
4E
4F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents