YASKAWA V1000 Technical Manual page 265

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

LED Operator Display
Cause
Input power phase loss.
One of the drive input power wiring
terminals is loose.
There is a problem with the voltage from the
drive input power.
The power has been interrupted.
Drive internal circuitry has become worn.
The drive input power transformer is not
large enough and voltage drops after
switching on power.
Air inside the drive is too hot.
Problem with the CHARGE indicator.
LED Operator Display
Cause
L2-02 changed from its default value in drive
that is 7.5 kW or smaller without installing a
Momentary Power Loss Ride-Thru.
The wiring for the control power supply is
damaged.
Internal circuitry is damaged.
LED Operator Display
Cause
The contactor on the inrush prevention
circuit is damaged.
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
DC Bus Undervoltage
One of the following conditions occurred while the drive was in operation:
• Voltage in the DC bus fell below the undervoltage detection level (L2-05).
Uv1
• For 200 V class: approximately 190 V (160 V for single phase drives)
• For 400 V class: approximately 380 V (350 V when E1-01 is less than 400) The fault is output only
if L2-01 = 0 or L2-01 = 1 and the DC bus voltage is under L2-05 for longer than L2-02.
• The main circuit drive input power is wired incorrectly.
• Correct the wiring.
• Ensure there are no loose terminals.
• Apply the tightening torque specified in this manual to fasten the terminals.
and Tightening Torque on page 56
• Check the voltage.
• Correct the voltage to within range listed in drive input power specifications.
Correct the drive input power.
• Check the maintenance time for the capacitors (U4-05).
• Replace the drive if U4-05 exceeds 90%.
Check the capacity of the drive input power transformer.
Check the drive internal temperature.
Replace the drive.
Control Power Supply Voltage Fault
Uv2
Voltage is too low for the control drive input power.
Correct parameter L2-02 setting or install optional Momentary Power Loss Ride-Thru unit.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
Undervoltage 3 (Inrush Prevention Circuit Fault)
Uv3
The inrush prevention circuit has failed.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
• Check monitor U4-06 for the performance life of the inrush prevention circuit.
• Replace the drive if U4-06 exceeds 90%.
Fault Name
Possible Solution
for details.
Fault Name
Possible Solution
Fault Name
Possible Solution
6.4 Fault Detection
Refer to Wire Gauges
6
265

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents