E3-01 (Motor 2 Control Mode) Dependent Parameters - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

u

E3-01 (Motor 2 Control Mode) Dependent Parameters

Table B.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
Parameter
E3-04
Maximum output frequency
E3-05
Maximum output voltage
E3-06
Base Frequency
E3-07
Middle output frequency
E3-08
Middle output freq. voltage
E3-09
Minimum output frequency
E3-10
Minimum output voltage
E3-11
Middle output frequency 2
E3-12
Middle output freq. voltage 2
<1>
E3-13
Base voltage
E3-14
Motor 2 Slip compensation gain
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<2> The default value is for the following localized drives: Japan (Model code: CIMR-VAoA) and Asia (Model code: CIMR-VToA)
China Localized Drive Default Values on page 381
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Description
<1>
<1>
<1>
<1>
for the default values of China localized (Model code: CIMR-VBoA) drives.
B.3 Control Mode Dependent Parameter Default Values
Setting Range
Resolution
40.0 to 400.0
0.1 Hz
0.0 to 255.0
0.1 V
0.0 to 400.0
0.1 Hz
0.0 to 400.0
0.1 Hz
0.0 to 255.0
0.1 V
0.0 to 400.0
0.1 Hz
0.0 to 255.0
0.1 V
0.0 to 400.0
0.1 Hz
0.0 to 255.0
0.1 V
0.0 to 255.0
0.1 V
0.0 to 2.5
Control Modes (E3-01)
V/f (0)
60.0
<2>
200.0
60.0
<2>
3.0
<2>
16.0
1.5
12.0
<2>
0.0
0.0
0.0
0.1
0.0
OLV (2)
60.0
<2>
200.0
60.0
<2>
3.0
<2>
12.0
0.5
2.5
<2>
0.0
0.0
0.0
1.0
.Refer to
B
379

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents