YASKAWA V1000 Technical Manual page 72

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

3.11 Braking Resistor
L8-01: Internal Dynamic Braking Resistor Protection Selection
L3-04: Stall Prevention During Deceleration
Note:
Select either 0 or 3
8.
Operate the system and verify the required deceleration rate is obtained during dynamic braking or stopping.
72
Table 3.16 Braking Resistor Settings
Parameter
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Settings
0: Disabled. The drive will not provide overheat protection.
Supply separate means of overheat protection.
1: Enabled. Braking Resistor is protected from overheat.
0: Stall prevention disabled.
3: Stall prevention enabled with a braking resistor
Note:
This setting cannot be used in OLV control for PM
motor.