Subchart A2: High Performance Operation Using Open Loop Vector Motor Control - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

u

Subchart A2: High Performance Operation Using Open Loop Vector Motor Control

Figure
4.8, Flowchart A2, describes Open Loop Vector Control for high-performance motor operation. This is appropriate
for applications requiring high starting torque, torque limits, and improved speed regulation.
Enter the data from the motor data
Figure 4.8 Flowchart A2: High Performance Operation Using Open Loop Vector Motor Control
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
NO
NO
Motor test report/ data
sheet available?
YES
sheet to E2-oo parameters.
YES
Is the motor cable
longer than 50 m?
Perform Stationary Auto-Tuning for
NO
From
Flowchart
A
YES
Possible for motor to
rotate during tuning? <1>
<1> Rotational tuning should
be performed with the
load disconnected
Calculate necessary E2-oo
parameter data using the
nameplate information.
terminal resistance (T1-01 = 2)
Return to
Flowchart
A