5.7 H: Terminal Functions
No.
H6-02
<1> Setting range is determined by drive software version.
PRG: 1016 and later: 100 to 32000 Hz
PRG: 1015 and earlier: 1000 to 32000 Hz
n
H6-03: Pulse Train Input Terminal RP Gain
Sets the level of the value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to terminal
RP.
No.
H6-03
n
H6-04: Pulse Train Input Terminal RP Bias
Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.
No.
H6-04
n
H6-05: Pulse Train Input Terminal RP Filter Time
Sets the pulse train input filter time constant in seconds.
The pulse train input filter helps prevent noise interference from causing erroneous operation when operating the drive
within the pulse train signal.
Increasing the filter setting time increases the effectiveness of the noise prevention, however, this also increasingly slows
drive response time.
No.
H6-05
n
H6-06: Pulse Train Output Terminal MP Monitor Selection
Selects the pulse train monitor output terminal MP function. The set value ooo is equal to the numerals in Uo-oo of
the selected monitor.
Refer to U: Monitors on page 371
listed below.
No.
H6-06
Pulse Train Output Terminal MP Monitor Selection
n
H6-07: Pulse Train Output Terminal MP Monitor Scaling
Pulse train monitor scaling sets the output frequency at terminal MP when the monitor item is 100%. Set H6-06 to 102
and H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
No.
H6-07
202
Name
Pulse Train Input Scaling
Name
Pulse Train Input Gain
Name
Pulse Train Input Bias
Name
Pulse Train Input Filter Time
Name
Name
Pulse Train Input Monitor Scaling
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
for a complete list of monitors. Selectable monitor items are
000, 031, 101, 102, 105,
116, 501, 502, 801 to 809
Setting Range
<1>
Setting Range
0.0 to 1000.0%
Setting Range
-100.0 to 100.0%
Setting Range
0.00 to 2.00 s
Setting Range
Setting Range
0 to 32000 Hz
Default
1440 Hz
Default
100.0%
Default
0.0%
Default
0.10 s
Default
102
Default
1440 Hz