5.7 H: Terminal Functions
Speed agree 1
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 216
width.
Setting 3: User Set Speed Agree 1 (f
Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-02) of
the programmed Speed Agree Level (L4-01).
Status
Open
Output frequency or frequency reference are outside the range of L4-01 ± L4-02.
Closed
Output frequency and the frequency reference are both with in the range of L4-01 ± L4-02.
Note:
The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
Frequency
reference
User Set
Speed Agree 1
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 216
width.
Setting 4: Frequency Detection 1
Output is closed as long as the output frequency is below the detection level set in L4-01 plus the hysteresis set in L4-02.
It closes when the output frequency falls below L4-01.
Status
Open
Output frequency exceeded L4-01 + L4-02.
Closed
Output frequency is below L4-01 or has not exceeded L4-01 + L4-02.
Note:
The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
188
Frequency
reference
Output
frequency
OFF
ON
Figure 5.57 Speed Agree 1 Time Chart
/f
Agree 1)
ref
set
Output
frequency
OFF
ON
Figure 5.58 User Set Speed Agree 1 Time Chart
L4-02
Description
L4-01
+/- L4-02
Frequency
reference
OFF
ON
Description
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
L4-02
for details on setting the detection
Output
frequency
L4-01
+/- L4-02
for details on setting the detection