YASKAWA V1000 Technical Manual page 355

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

No.
Name
Analog Input Filter Time
H3-13
Constant
H3-14
Analog Input Terminal
<3>
Enable Selection
H3-16
Terminal A1 Offset
<3>
H3-17
Terminal A2 offset
<3>
<1> The availability of certain parameters depends on the control method used.
<2> Parameter can be changed during Run.
<3> Parameter available in drive software versions PRG: 1016 and later.
H3-oo
Function
Setting
0
Frequency Bias
1
Frequency Gain
Auxiliary Frequency Reference (used as a
2
Multi-Step Speed 2)
4
Output Voltage Bias
7
Overtorque/Undertorque Detection Level
B
PID Feedback
C
PID Set Point
E
Motor Temperature (PTC input)
F
Not used/Through Mode
10
FWD Torque Limit
11
REV Torque Limit
12
Regenerative Torque Limit
15
FWD/REV Torque Limit
16
Differential PID Feedback
30/31
DWEZ Analog Input 1/2
41
Output Voltage Gain
<1>
<1> Parameter available in drive software versions PRG: 1016 and later.
No.
Name
Multi-Function Analog
H4-01
Output Terminal AM
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Description
Sets the primary delay filter time constant for terminals A1
and A2. Used for noise filtering.
Determines which analog input terminal will be enabled
when a digital input programmed for "Analog input enable"
(H1-oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
7: All terminals enabled
Enter a 0 V signal to terminal A1. Next adjust the offset in
H3-16 until the monitor U1-13 for the terminal A1 input
voltage reads 0.0%. The process is the same for terminal
A2.
Enter a 0 V signal, and adjust the offset for terminal A2 in
H3-17 until the monitor U1-14 for terminal A2 input
voltage reads 0.0%.
H3 Multi-Function Analog Input Settings
Max output frequency (E1-04).
Same value can be set using H3-02 and H3-10.
10 V = 100%
Maximum output frequency (E1-04)
Motor rated voltage (E1-05).
Open Loop Vector: Motor rated torque
V/f Control: Drive rated current
10 V = 100%
10 V = 100%
10 V = 100.00%
Motor rated torque
Motor rated torque
Motor rated torque
Motor rated torque
10 V = 100%
Depending on function.
10 V = 100%
Description
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
Uo-oo. For example, enter "103" for U1-03.
When using this terminal in through mode or when not using
it at all, set "000" or "031".
Range
0.00 to
2.00
1, 2, 7
-500 to 500
-500 to 500
Maximum Input Level Possible
Range
000 to
999
<1>
B.2 Parameter Table
Control
Mode
Addr.
Def.
Pg.
O
Hex
V/
P
L
f
M
V
0.03 s A A A
41B
198
7
A A A
41C
200
0
A A A
440
200
0
A A A
441
200
Control
Mode
Pg.
O
V/
P
L
f
M
V
O
O
O
198
O
O
O
199
O
O
O
199
O
199
O
O
O
199
O
O
O
199
O
O
O
199
O
O
O
199
O
O
O
199
O
199
O
199
O
199
O
199
O
O
O
199
O
O
O
200
O
199
Control
Mode
Addr.
Def.
Pg.
O
Hex
V/
P
L
f
M
V
102
A A A
41D
200
355
B