YASKAWA V1000 Technical Manual page 198

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

5.7 H: Terminal Functions
Setting 1: 0 to 10 Vdc without Lower Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted. Refer to the explanation of H3-01, Setting 1.
to Setting 1: 0 to 10 Vdc without Limit on page 195
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
Settings on page 198
for a list of functions and descriptions.
No.
H3-10
n
H3-11/H3-12: Terminal A2 Gain/Bias Setting
Parameter H3-11 sets the level of the selected input value that is equal to 10 Vdc/20 mA input at terminal A2 (Gain).
Parameter H3-12 sets the level of the selected input value that is equal to 0 Vdc/4 mA/0 mA input at terminal A2.
Both can be used to adjust the analog input A2 characteristics. The setting works in the same way as parameters H3-03/04
for analog input A1.
No.
H3-11
H3-12
n
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to both analog inputs A1 and A2.
No.
H3-13
An analog input filter can be used to prevent erratic drive control when a "noisy" analog reference is used. The drive
operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog
signals.
n
Multi-Function Analog Input Terminal Settings
This section describes the various functions that can be assigned to terminals A1 and A2 by setting H3-02 and H3-10.
Note:
The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when
selecting and adjusting analog input functions.
Setting
0
Frequency Bias
1
Frequency Gain
2
Auxiliary Frequency Reference
4
Output Voltage Bias
7
Overtorque/Undertorque Detection Level
B
PID Feedback
C
PID Set Point
E
Motor Temperature (PTC input)
F
Not used/Through Mode
<1> Available in drive software versions PRG: 1016 and later.
Setting 0: Frequency Bias
The input value of an analog input set to this function will be added to the analog frequency reference value. Use this
setting also when only one analog input is used to supply the frequency reference.
By default both analog inputs A1 and A2 are set for this function. Using both A1 and A2 at the same time increases the
frequency reference by the total of both inputs.
Example: If the analog frequency reference by analog input A1 is 50% and a bias of 20% is applied by analog input A2,
the resulting frequency reference will be 70% of the maximum output frequency.
198
Name
Terminal A2 Function Selection
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Name
Analog Input Filter Time Constant
Table 5.28 Multi-Function Input Terminal Settings
Function
Refer to Multi-Function Analog Input Terminal
Page
Setting
198
10
Forward Torque Limit
199
11
Reverse Torque Limit
199
12
Regenerative Torque Limit
199
15
General Torque Limit
199
16
Differential PID Feedback
199
30
DriveWorksEZ Analog Input 1
199
31
DriveWorksEZ Analog Input 2
199
<1>
Output Voltage Gain
41
199
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Setting Range
0 to 31
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0.00 to 2.00 s
Function
Refer
Default
0
Default
100.0%
0.0%
Default
0.03 s
Page
199
199
200
200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents