5.2 b: Application
The PID acceleration/deceleration time can be canceled using a digital input programmed for "PID SFS cancel" (H1-
oo = 34).
No.
b5-17
n
b5-18: PID Setpoint Selection
Enables or disables parameter b5-19 for PID setpoint.
No.
b5-18
Setting 0: Disabled
Parameter b5-19 is not used as the PID setpoint. The setpoint must be entered via an analog input, pulse input, or
MEMOBUS/Modbus register 06H.
Setting 1: Enabled
Parameter b5-19 is used as PID setpoint.
n
b5-19: PID Setpoint Value
Used to adjust the PID setpoint if parameter b5-18 = 1.
No.
b5-19
n
b5-20: PID Setpoint Scaling
Determines the units that the PID setpoint (b5-19) is set in and displayed. Also determines the units for monitors U5-01
and U5-04.
No.
b5-20
Setting 0: Hz
The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: %
The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min
The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined
The setpoint b5-19 and PID monitors U1-01/04 are displayed with the unit and resolution defined by parameters b5-38
and b5-39.
n
b5-34: PID Output Lower Limit
Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower
limit is disabled when set to 0.00%
No.
b5-34
n
b5-35: PID Input Limit
Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1–04). Parameter b5-35 acts
as a bipolar limit.
No.
b5-35
n
b5-38/39 PID Setpoint/Monitor User Display Value/Display Digits
When parameter b5-20 is set to 3, the parameters b5-38 and b5-39 can be used to set a user defined display for the PID
setpoint (b5-19) and feedback monitors (U5-01/04).
Parameter b5-38 determines the display value when the maximum frequency is output. Parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
138
Name
PID Accel/Decel Time
Parameter Name
PID Setpoint Selection
Name
PID Setpoint Value
Parameter Name
PID Setpoint Scaling
Name
PID Output Lower Limit
Name
PID Input Limit
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Setting Range
0 to 255 s
Setting Range
0 or 1
Setting Range
0.00 to 100.00%
Setting Range
0 to 3
Setting Range
-100.0 to 100.0%
Setting Range
0.0 to 1000.0%
Default
0 s
Default
0
Default
0.00%
Default
1
Default
0.00%
Default
1000.0%