Parameter Table; Parameter Table; A: Initialization Parameters - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

B.2 Parameter Table
An "A" in the "Control Mode" column indicates that the parameter is available in the Advanced menu of the respective
control mode.
An "S" in the "Control Mode" column indicates that the parameter is available in the Startup menu of the respective control
mode.
A "–" in the "Control Mode" column indicates that the parameter is NOT available in the respective control mode.
An "O" in the "Control Mode" column indicates that the multi-function selection is available in the respective control
mode.
u

A: Initialization Parameters

The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
No.
Name
A1-00
Language Selection
<1> <2>
A1-01
Access Level
<1> <3>
Selection
A1-02
Control Method
<2>
Selection
A1-03 Initialize Parameters
A1-04 Password
A1-05 Password Setting
A1-06 Application Preset
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Description
A1: Initialization Parameters
Use A1 parameters to configure the basic environment for drive operation.
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
Selects which parameters are accessible via the digital operator.
0: Operation only
1: User Parameters (access to a set of parameters selected by the
user)
2: Advanced Access Level
Selects the Control Method of the drive. Auto-Tuning must be
performed when selecting one of the vector control modes.
0: V/f Control without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
Note: 1. Does not return to the default setting after initialization.
2. If using Open Loop Vector Control (A1-02 = 2), then Auto-
Tuning must be performed again after the drive is initialized.
Refer to Auto-Tuning on page 100
Resets all parameters to factory default settings. (Initializes the
drive then returns A1-03 to 0)
0: No Initialization
1110: User Initialize
(First set user parameter values must be stored using parameter
o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
5550: oPE04 Error Reset
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03, A1-06, and A2-01
through A2-32 cannot be changed.
Sets parameters that are commonly used in certain applications to
A2-01 through A2-16 for easier access.
0: General-purpose (A2 parameters are not affected)
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Elevator
7: Hoist
<4>
8: Conveyor 2
Range
for details.
0 to 5550
The following parameters are not reset when
the performing initialization: A1-00, A1-02,
A1-07, E1-03, E5-oo, F6-08, L8-35, o2-04,
o2-09, and all U2 and U3 monitors.
0 to 9999
0 to 9999
This parameter is hidden from view. To
access A1-05, first display A1-04. Then
press the STOP key while holding down
the up arrow key. Parameter A1-05 will
appear.
B.2 Parameter Table
Control
Mode
Addr.
Def.
O
Hex
V/
P
L
f
M
V
<6>
0 to 7
A A A
0 to 2
2
A A A
0, 2, 5
0
S
S
S
0
A A A
0
A A A
0
A A A
0 to 8
0
A A A
Pg.
100
112
101
112
102
112
103
113
104
114
105
114
B
127
94
331