YASKAWA V1000 Technical Manual page 421

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Register No.
Output Terminal Status
bit 0
002DH
bit 1
bit 2
bit 3 to bit F
002EH
Reserved
002FH
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H
Reserved
0031H
DC Bus Voltage, 1 Vdc units
0032H
Torque Monitor, 1% units
0033H
Reserved
0034H
Product Code 1 [ASCII], Product Type (V0 for V1000)
0035H
Product Code 2 [ASCII], Region Code
0036H to 0037H
Reserved
0038H
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H
PID Input, 0.1% units, signed, 100% / max. output frequency
003AH
PID Output, 0.1% units, signed, 100% / max. output frequency
003BH to 003CH
Reserved
Communications Error Log
bit 0
bit 1
bit 2
003DH
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
003EH
Output Frequency
003FH
0040H to 004AH
Used for various monitors U1-oo.
Drive status (U1-12)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
004BH
bit 6
bit 7
bit 8
bit 9
bit A
bit B to D
bit E
bit F
004CH to 007EH
Used for various monitors U1-oo, U4-oo, U5-oo and U6-oo.
007FH
Alarm Code,
Used for monitors U2-oo, U3-oo.
0080H to 0097H
Contents on page 426
U4-01 (Cumulative Operation Time)
0098H, 0099H
Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.
U4-03 (Cooling Fan Operation Time)
009AH, 009BH
Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.
00ABH
Drive Rated Current
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Multi-Function Contact Output (terminal MA/MB-MC)
Multi-Function Photocoupler Output 1 (terminal P1 - PC)
Multi-Function Photocoupler Output 2 (terminal P2 - PC)
Reserved
<3>
CRC Error
Data Length Error
Reserved
Parity Error
Overrun Error
Framing Error
Timeout
Reserved
<4>
r/min
0.01% units
Refer to U: Monitors on page 371
During Run
During Zero Speed
During Reverse Run
During Fault Reset Signal Input
During Speed Agree
Drive Ready
Alarm
Fault
During Operation Error (oPEoo
During Momentary Power Loss
Motor 2 selected
Reserved
ComRef status, NetRef status
ComCtrl status, NetCtrl status
Refer to Alarm Register Contents on page 427
Refer to U: Monitors on page 371
for register value descriptions.
<2>
C.10 MEMOBUS/Modbus Data Table
Contents
for parameter details.
Refer to U: Monitors on page 371
for alarm codes.
for parameter details and
for parameter details.
Refer to Fault Trace
C
421