o2-03: User Parameter Default Value
Once drive parameters are set up completely, the values set can be saved as "User Initialization Values" by setting parameter
o2-03. Once this has been done, the "Initialize Parameters" parameter (A1-03) will offer the choice of "1110: User
Initialize". Choosing A1-03 = "1110: User Initialize", will reset all parameters to the values saved as "User Initialization
Values".
Refer to A1-03: Initialize Parameters on page 113
No.
o2-03
Setting 0: No Change
All "User Initialization Values" are saved as they are.
Setting 1: Set User Initialization Values
The current parameter settings are saved as "User Initialization Values". After setting o2-03 to 1 and pressing the ENTER
key, the values are saved and the display returns to 0.
Setting 2: Clear User Initialization Values
All "User Initialization Values" are cleared. After setting o2-03 to 2 and pressing the ENTER key, the values are erased
and the display returns to 0. A1-03 = 1110 becomes invalid.
n
o2-04: Drive Model Selection
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal
performance and proper protection for the drive hardware. This parameter is configured at the factory and does not normally
require adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.
No.
o2-04
Note:
1.
Refer to Defaults by Drive Model and Duty Rating (ND/HD) on page 382
depending on the drive model selection.
2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly.
3. This parameter is not reset to the default value when the drive is initialized using A1-03.
n
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be used to input a frequency reference from the digital operator.
No.
o2-05
Frequency Reference Setting Method Selection
Setting 0: ENTER Key Required
Every change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key
before it becomes effective.
Setting 1: ENTER Key Not Required
The output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator.
The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key
has been released. If an undervoltage error (Uv) occurs within 5 seconds of pressing the ENTER key, the frequency
reference will not be saved to memory. The digital operator display flashes when settings can be made to the frequency
reference.
n
o2-06: Operation Selection when Digital LCD Operator is Disconnected
Determines if the drive will stop when an external LCD operator is removed in LOCAL mode or with b1-02 set to 0.
Note:
An LCD operator is available as an option. This setting is not applicable to the standard LED operator that comes with the drive.
No.
o2-06
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Name
User Parameter Default Value
Name
Drive Model Selection
Name
Figure 5.91 Ready to Set Frequency Reference
Name
Digital Operator Disconnection Operation
5.10 o: Operator Related Settings
for details on drive initialization.
Setting Range
0 to 2
Setting Range
for a list of o2-04 settings and parameters that change
Setting Range
0 or 1
Setting Range
0 or 1
Default
0
Default
Depending on
-
drive size
Default
0
Default
0
5
237