Advertisement

5.10 o: Operator Related Settings
Setting 0: Continue Operation
The operation is continued.
Setting 1: Trigger a Fault
The operation is stopped and an oPr fault is triggered. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up when the Run command is set to be given from
the digital operator.
Note:
This parameter is effective only when the Run command is set to be given from the digital operator (b1-02/16 = 0).
No.
o2-07
Motor Direction at Power Up when Using Operator
Setting 0: Forward
Setting 1: Reverse
u

o3: Copy Function

Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive.
n
o3-01: Copy Function Selection
This parameter controls the copying of parameters to and from the LED operator (option). The copy function will change
certain parameter default settings depending on the regional specification of the drive.
No.
o3-01
0: COPY SELECT (no function)
1: INV --> OP READ
All parameters are copied from the drive to the digital operator.
Note:
Set o3-02 to 1 to unlock copy protection.
2: OP --> INV WRITE
All parameters are copied from the digital operator to the drive.
3: OP<-->INV VERIFY
Parameter settings in the drive are compared to those in the digital operator.
Note:
When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur.
n
o3-02 Copy Allowed Selection
Enables and disables the digital operator copy functions.
No.
o3-02
0: Disabled
No digital operator copy functions are allowed
1: Enabled
Copying allowed
u

o4: Maintenance Monitor Settings

n
o4-01: Accumulated Operation Time Setting
Parameter o4-01 sets the cumulative operation time and allows the user to set the starting value of the accumulated operation
time displayed in monitor U4-01.
Note:
The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will
also be displayed in monitor U4-01.
No.
o4-01
238
Name
Name
Copy Function Selection
Name
Copy Allowed Selection
Name
Accumulated Operation Time Setting
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Setting Range
0 or 1
Setting Range
0 to 3
Setting Range
0, 1
Setting Range
0 to 9999
Default
0
Default
0
Default
0
Default
0