Application Selection; Application Selection; Setting 1: Water Supply Pump Application - YASKAWA V1000 Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

4.6 Application Selection

4.6

Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically sets the required parameters to the Application Preset default values and selects I/Os.
In addition, the parameters most likely to be changed are assigned to the list of User Parameters, A2-01 through A2-16.
These can be accessed in the Setup Mode and provide quicker application adjustment by eliminating the need to scroll
through multiple menus.
The following presets can be selected:
Note:
1. Do not set any value outside the allowable range for A1-06. Setting an out-of-range value will cause "APPL" to flash on the display
in the Setup group and disable the up and down arrow keys on the digital operator. To fix this error, press the ESC key to return to
the Setup group and then it will then be possible to switch to another mode using the up and down arrow keys.
2. A1-06 setting can only be changed by initializing the drive by first setting A1-03 to 2220. Setting A1-06 to a value that is out of
range will not adversely affect drive operation. When the drive should not be initialized because initialization will cause other
problems, then A1-06 does not need to be changed.
WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change
the I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.
No.
A1-06
<1> Available in drive software versions PRG: 1020 and later.
u

Setting 1: Water Supply Pump Application

No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Drive Duty Selection
E1-03
V/f Pattern Selection
E1-07
Middle Output Frequency
E1-08
Middle Output Frequency Voltage
L2-01
Momentary Power Loss Operation Selection
L3-04
Stall Prevention Selection during Deceleration
No.
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
E1-03
V/f Pattern Selection
E1-07
Middle Output Frequency
94
Parameter Name
Application Presets
Table 4.5 Water Supply Pump Parameter Settings
Name
Table 4.6 Water Supply Pump: User Parameters (A2-01 to A2-16)
Parameter Name
0: Disabled
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
6: Hoist
7: Traveling
8: Conveyor 2
0: V/f Control
1: Reverse Prohibited
1.0 s
1.0 s
1: Normal Duty
0FH
30.0 Hz
50.0 V
1: Enabled
1: Enabled
No.
E1-08
Middle Output Frequency Voltage
E2-01
Motor Rated Current
Multi-Function Digital Input Terminal S5 Function
H1-05
Selection
Multi-Function Digital Input Terminal S6 Function
H1-06
Selection
Multi-Function Digital Input Terminal S7 Function
H1-07
Selection
L5-01
Number of Auto Restart Attempts
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
Setting Range
<1>
Default Setting
Parameter Name
Default
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents