Co: Cu Analog Inputs Input Voltage/Current Actual / Cu Ai U/I_Inp Act; Cu Analog Inputs Smoothing Time Constant / Cu Ai T_Smooth; Co: Cu Analog Inputs Actual Value In Percent / Cu Ai Value In % - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
r0752[0...3]

CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act

Access level: 2
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Displays the actual temperature in °C when set as temperature sensor and the voltage divider is switched in.
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Dependency:
The type of analog input AIx (voltage, current or temperature input) is set using p0756.
See also: p0756
Note
AI: Analog Input
X202: IO module terminal
p0753[0...3]

CU analog inputs smoothing time constant / CU AI T_smooth

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.0 [ms]
Description:
Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs.
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Note
AI: Analog Input
X202: IO module terminal
r0755[0...3]

CO: CU analog inputs actual value in percent / CU AI value in %

Access level: 2
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
566
Calculated: -
Scaling: p0514
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.0 [ms]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
0.0 [ms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
- [%]
SINAMICS G120X converter

Advertisement

Table of Contents
loading