p1110[0...n]

BI: Inhibit negative direction / Inhib neg dir

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to disable the negative direction.
Dependency:
See also: p1111
p1111[0...n]

BI: Inhibit positive direction / Inhib pos dir

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to disable the positive direction.
Dependency:
See also: p1110
r1112

CO: Speed setpoint after minimum limiting / n_set aft min_lim

Access level: 4
Can be changed: -
Unit group: 3_1
Min:
- [rpm]
Description:
Displays the speed setpoint after the minimum limiting.
Dependency:
See also: p1091, p1092, p1093, p1094, p1101
p1113[0...n]

BI: Setpoint inversion / Setp inv

G120X_DP,
Access level: 3
G120X_PN
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to invert the setpoint.
Dependency:
See also: r1198
CAUTION
If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using p1113
when the technology controller is enabled because this can cause the speed to change suddenly and lead to positive
couplings in the control loop.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.2 Parameter list
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2505, 3040
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2505, 3040
Factory setting:
0
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 3050
Factory setting:
- [rpm]
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2441, 2442,
2505, 3040
Factory setting:
[0] 2090.11
[1] 0
[2] 0
[3] 0