Parameters
7.2 Parameter list
p0644[0...n]

Current limit excitation induction motor / Imax excitat ASM

G120X_DP (PM330),
Access level: 3
G120X_PN (PM330),
Can be changed: T, U
G120X_USS (PM330)
Unit group: -
Min:
50.0 [%]
Description:
Maximum excitation current of the induction motor referred to the permissible rated current of the power unit (r0207[0]).
Dependency:
Only effective for vector control.
Note
The parameter is pre-assigned in the automatic calculation for chassis power units.
p0650[0...n]

Actual motor operating hours / Oper hours motor

Access level: 3
Can be changed: T
Unit group: -
Min:
0 [h]
Description:
Displays the operating hours for the corresponding motor.
The motor operating time counter continues to run when the pulses are enabled. When the pulse enable is withdrawn,
the counter is held and the value saved.
Dependency:
See also: p0651
See also: A01590
Note
For p0651 = 0, the operating hours counter is disabled.
The operating hours counter in p0650 can only be reset to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
p0651[0...n]

Motor operating hours maintenance interval / Mot t_op maint

Access level: 3
Can be changed: T
Unit group: -
Min:
0 [h]
Description:
Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate message is output when the operating hours set here are reached.
Dependency:
See also: p0650
See also: A01590
Note
For p0651 = 0, the operating hours counter is disabled.
When setting p0651 to 0, then p0650 is automatically set to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
r0719

IO extension module status / IO module status

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
IO expansion module status
558
Calculated: -
Scaling: -
Unit selection: -
Max:
300.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
4294967295 [h]
Calculated: -
Scaling: -
Unit selection: -
Max:
150000 [h]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
300.0 [%]
Data type: Unsigned32
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0 [h]
Data type: Unsigned32
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0 [h]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
SINAMICS G120X converter

Advertisement

Table of Contents
loading

Table of Contents