FANBPU. This section describes the procedure for removing the FANUs and FANBPU.
1.
Place the server in the cold state.
Stop the power supply to the server to place it in the cold state. For the
procedure for removing the power cords, see
Remove the front cover.
2.
For the procedure for removing the front cover, see
Cover."
Note - The serial number of the server is printed on a label affixed on the front cover. Store
this cover such that it is not mixed up with the front covers of other SPARC M12 units.
3.
Remove all the FANUs.
Remove all the FANUs mounted in the FANBPU. For details on the procedure,
see
"14.3.1 Removing a
Figure 16-2     Removing the FANUs
Remove the FANBPU.
4.
Loosen the three fixing screws, and remove the FANBPU. For details, see
Removing the
FANBPU."
Chapter 16 Maintaining the HDD Backplane Unit and Operation Panel
"9.8.2 Removing the Power
FANU."
Cords."
"9.8.3 Removing the Front
"14.3.2
423