Adam-4080 Counter/Frequency Input Module - Advantech Data Acquisition Modules ADAM 4000 User Manual

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

A.19 ADAM-4080 Counter/Frequency Input Module
Table A-23 ADAM-4080 Specifications
Input channel number
Input frequency
Input mode
Isolation input level
Logic level 0
Logical level 1
Isolation voltage
Non-isolation input level
Logic Ievel 0
Logic level 1
Input pulse width
Maximum count
Programmable digital
noise filter
Alarming
Preset type
Frequency measurement
Range
Programmable built-in
gate time
Digital output channels
Sink current
Power dissipation
Support protocol
Watchdog timer
Power requirements
Power consumption
2 independent 32-bit counters
50 kHz maximum
Isolated or non-isolated
+1 V maximum
+3.5 V to +30 V
2500 VRMS
Programmable threshold
0 to +5 V (default = 0.8 V)
0 to +5 V (default = 2.4 V)
>10 μsec
4,294,967,295 (32 bits)
2 μsec to 65 msec
Alarm comparators on each counter
Absolute or relative
5 Hz to 50 KHz
1.0/0.1 sec
2 channels open collector to 30 V
30 mA max. load
300 mW
ADAM ASCII
1.6 second (System)
+10 to +30 V
DC
2.0 W@ 24 V
DC
Appendix A Technical Specification A-45
Appendix A
(non-regulated)

Advertisement

Table of Contents
loading

Table of Contents