4069
$AAS
Name
Change and Read the Low Power Mode of Module command
Description
The command requests the module at address AA to change
and return the status of low power mode of module
Syntax
$AAS(cr)
$
is a delimiter character.
AA
address that you will access to.
S
command
(cr)
Response
!AAX(cr)
?AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
is a delimiter character which indicates a valid command
?
is a delimiter character which indicates an invalid command
AA
hexadecimal address of the module.
X
the logic is 1, it represents low power. However, if the logic
is 0, it is normal
(cr)
7-25 ADAM 4000 Series User's Manual
(range 00-FF) represents the 2-character hexadecimal
is the Change and Read the Low Power Mode of Module
is the terminating character, carriage return (ODh).
if the command was valid.
if an invalid command has been issued.
(range 00-FF) represents the calibrated 2-character
represents the Status bit from the low power status. When
is the terminating character, carriage return (0Dh).