4021
$AA4
Name
Start-up Voltage/Current Output Configuration command
Description
Stores the present output value of an analog output module
at address AA in the module's non-volatile register. The
output value will take effect at start-up or after a brownout.
Syntax
$AA4(cr)
$
AA
address of the analog output module whose output current
is to be set.
4
(cr)
Response
!AA(cr)
?AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
received.
?
invalid.
AA
address of the analog output module.
(cr)
Example
command: $0A4(cr)
response:
Presume the present output value of the analog output
module at address 0A is 9.4 mA. The command tells the
analog output module to store the present output value into
non-volatile memory. When the module is at start-up or
reset, its default output value will be 9.4mA. The response
of the analog output module indicates that the command
has been received.
NOTICE: An analog output module requires a maximum of 6 milli-seconds
after it received a Startup Voltage/Current Output Configuration
command to let the settings take effect . During this interval, the
module can not be addressed to perform any other actions.
6-8 ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Start-up Output Current Configuration command.
is the terminating character, carriage return (0Dh).
if the command is valid.
if an invalid command was issued.
delimiter character indicates that a valid command was
delimiter character indicates that the command was
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh).
!0A(cr)
Analog Output Module Command Set